Product Description
General Information
Parameter |
Value |
---|---|
Manufacturer |
Yokogawa |
Model/Part Number |
SDV144-S63 |
Product Description |
Digital Input Module (16-channel, 24 V DC, module isolation) |
Standard Specifications
Item |
Specification |
---|---|
Number of Inputs |
16-channel, module isolation (*3) |
Input Signal |
No-voltage contact |
ON Resistance |
1 kΩ maximum |
OFF Resistance |
100 kΩ minimum |
Input Current |
6 mA ± 20% (External power supply, 24 V DC at 0 Ω input) |
Contact Rating |
24 V DC +20% / -10%, 10 mA or greater |
External Power Supply |
24 V DC +20% / -10% (*3) (*4) |
Current Capacity |
200 mA |
Instantaneous Maximum Permissible Input Voltage |
30.0 V DC |
Input Response Time |
40 ms maximum |
Withstand Voltage |
2 kV AC between input signal and system for 1 minute, 16-input line collectively connected (*5) |
Current Consumption |
290 mA max (5 V DC) / 140 mA max (24 V DC) |
Weight |
Approx. 0.36 kg (For pressure clamp terminal block or MIL cable) Approx. 0.41 kg (With signal cable interface adapter) |
External Connection |
Pressure clamp terminal / MIL cable / Dedicated signal cable (AKB331) |
Model Variations & Options
Model Variations (Suffix Codes)
Suffix Code |
Description |
---|---|
-S |
Standard type |
5 |
For pressure clamp terminal block or MIL cable (no explosion protection) |
6 |
With signal cable interface adapter (no explosion protection) (*1) |
E |
For pressure clamp terminal block or MIL cable (explosion protection) |
F |
With signal cable interface adapter (explosion protection) (*1) |
3 |
With ISA Standard G3 and temperature range (-20 to 70 °C) |
C |
With ISA Standard G3 and high-density installation (-20 to 70 ºC) |
Option Codes
Option Code |
Description |
---|---|
/B4S00 |
With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00] |
/B4S10 |
With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10] |
/B4D00 |
With dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*2) [Model: STB4D-00] |
/B4D10 |
With dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*2) [Model: STB4D-10] |
/PRP |
With prevention pin of false insertion (*3) |
/CCC01 |
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01] |
/CCC02 |
With connector cover for MIL cable (for discrete wire) [Model: SCCC02] |
Check below popular items for more information in | Industrial Control Hub | |||
Brand | Description | Price (USD) | Stock | Link |
YOKOGAWA | AAI543-H00 S1 Analog Output Module | 643-1643 | 448 | AAI543-H00 S1 Analog Output Module |
YOKOGAWA | YS170-012 S4 Single-Loop Programmable Controller | 1357-2357 | 224 | YS170-012 S4 Programmable Controller |
YOKOGAWA | AAI135-H50/K4A00 Analog Input Module | 1714-2714 | 961 | AAI135-H50/K4A00 Analog Input Module |
YOKOGAWA | AAI143-H50/A4S00 Analog Input Module | 1000-2000 | 851 | AAI143-H50/A4S00 Analog Input Module |
YOKOGAWA | AMN12T S2 Analog I/O Module Nest | 500-1500 | 232 | AMN12T S2 Analog I/O Module Nest |
YOKOGAWA | AAP135-S50/13S00 Pulse Input Module | 857-1857 | 948 | AAP135-S50/13S00 Pulse Input Module |
YOKOGAWA | PW302 S4 Power Supply Module | 500-1219 | 664 | PW302 S4 Power Supply Module |