Product Description
General Information
Manufacturer |
Yokogawa |
---|---|
Model/Part Number |
SDV144-S33 S2 |
Description |
Digital Input Module |
Item Specifications
Item |
Specification |
---|---|
Number of Inputs |
16-channel, module isolation (*3) |
Input Signal |
No-voltage contact |
ON Resistance |
1 kΩ maximum |
OFF Resistance |
100 kΩ minimum |
Input Current |
6 mA ± 20 % (External power supply, 24 V DC at 0 Ω input) |
Contact Rating |
24 V DC +20 % / -10 % (*4), 10 mA or greater |
External Power Supply |
24 V DC +20 % / -10 % (*3) (*4) |
Current Capacity |
200 mA |
Instantaneous Maximum Permissible Input Voltage |
30.0 V DC |
Input Response Time |
40 ms maximum |
Withstand Voltage (*1) (*2) |
2 kV AC between input signal and system for 1 minute, 16-input line collectively connected (*5) |
Current Consumption |
290 mA maximum (5 V DC), 140 mA maximum (24 V DC) |
Weight |
Approx. 0.36 kg (For pressure clamp terminal block or MIL cable), Approx. 0.41 kg (With signal cable interface adapter) |
External Connection |
Pressure clamp terminal, MIL cable, Dedicated signal cable (AKB331) |
Model and Suffix Codes
Description |
Model |
Suffix Code |
Specification |
---|---|---|---|
Digital Input Module (16-channel, 24 V DC, module isolation) |
SDV144 |
-S |
Standard type |
5 |
For pressure clamp terminal block or MIL cable with no explosion protection |
||
6 |
With signal cable interface adapter and no explosion protection (*1) |
||
E |
For pressure clamp terminal block or MIL cable with explosion protection |
||
F |
With signal cable interface adapter and explosion protection (*1) |
||
3 |
With ISA Standard G3 and temperature (-20 to 70 °C) |
||
C |
With ISA Standard G3 and high-density installation (-20 to 70 ºC) |
Option Codes
Option Code |
Description |
---|---|
/B4S00 |
With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00] |
/B4S10 |
With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10] |
/B4D00 |
With dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*2) [Model: STB4D-00] |
/B4D10 |
With dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*2) [Model: STB4D-10] |
/PRP |
With prevention pin of false insertion (*3) |
/CCC01 |
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01] |
/CCC02 |
With connector cover for MIL cable (for discrete wire) [Model: SCCC02] |
Check below popular items for more information in | Industrial Control Hub | |||
Brand | Description | Price (USD) | Stock | Link |
YOKOGAWA | ADV151-P00 Digital Input Module | 500-800 | 319 | ADV151-P00 Digital Input Module |
YOKOGAWA | NFSB100-S50 SB Bus Repeat Module | 1500-2500 | 626 | NFSB100-S50 SB Bus Module |
YOKOGAWA | SDV144-S63 S4 Digital Input Module | 1571-2571 | 215 | SDV144-S63 S4 Digital Input Module |
YOKOGAWA | AAI543-S53/K4A00 Analog Output Module | 1214-2214 | 622 | AAI543-S53/K4A00 Analog Output Module |
YOKOGAWA | AEP7D-25 Primary Power Supply Bus Unit | 500-1500 | 973 | AEP7D-25 Power Supply Bus Unit |
YOKOGAWA | AFV10D-S41401 Duplexed Field Control Unit | 2357-3357 | 852 | AFV10D-S41401 Field Control Unit |
YOKOGAWA | ALP111-S01 PROFIBUS-DP Communication Module | 2071-3071 | 140 | ALP111-S01 PROFIBUS-DP Module |