Product Description
Product Information: Triconex EMP II 3006 Main Processor Module
Manufacturer:
- Triconex
Model/Part Number:
- EMP II 3006 (Main Processor Module)
Specifications
Feature | Specification |
---|---|
Central Processor | National NS32GX32, 32 bits, 25 MHz |
Math Co-Processor | National NS32381, 32 bits, 25 MHz |
EPROM Memory | 512 KB |
SRAM | Model 3006: 2 MB, Model 3007: 1 MB |
Clock Calendar | Time and date with Battery backup |
Typical Drift | ±2 seconds per day |
Maximum Drift | ±8.6 seconds per day |
TriBus | 4 megabits per second, 16-bit DMA |
Serial Port | Optically isolated RS-232 interface, 25-pin connector, 500 VDC isolation for diagnostic analysis |
Communication Processor | Intel 80C152 32 KB EPROM, 64K shared memory interface, 16 MHz |
Communication Interface | RS-485 protocol, Baud Rate: 2 megabits per second |
I/O Processor | Intel 80C31, 12 MHz, 32 KB EPROM, 64K shared memory interface |
I/O Interface Protocol | RS-485 protocol, Baud Rate: 375 kilobits per second |
Logic Power | 15 W |
Status Indicator Conditions and Actions
Indicator Condition | Description | Action |
---|---|---|
Green steady, No light | The module is operating normally. The ACTIVE indicator blinks once per scan when executing a control program. | No action required. |
Green steady, No light (Maintenance Mode) | No control program has been loaded, or it is in education mode by other MPs. | Replace the module if ACTIVE indicator does not turn on after a few minutes. |
Off, Red steady | The module has failed. | Replace the module. |
Red blinking | The MP is re-educating. | Wait for the PASS indicator to turn on, followed by the ACTIVE indicator. |
Green steady, Red steady (High Error) | The MP soft error count is very high. | Replace the module at the first opportunity. |
Off, Off | The indicators or signal circuitry are malfunctioning. | Replace the module |