Product Description
Manufacturer: BACHMANN
Model/Part Number: SLC284
Description: Safety processor module
Item Numbers:
-
SLC284: 00014273-00
-
SLC284❉: 00017465-00
Processor
-
CPU: 2x LPC2468, 72 MHz, 32 bit
Controller
-
Programming via controller (I/O bus) or serial interface (COM)
-
Number of independent safety programs per SLC: 1
-
Program cycle minimal: 5 ms
-
I/O expansion via: SDI208 or SDO204 modules
Digital Inputs
-
Quantity: 16 digital inputs - can be used redundantly in pairs (PL e/SIL3/Cat 4)
-
Input voltage range (H): 15 .. 34 V DC
-
Input voltage range (L): -34 .. +5 V DC
-
Input delay (HW): 300 µs
-
Input delay (SW): 1 ms with deactivated test clocking
-
Input type: According to IEC61131-2
-
Input current (at least): Type 1, 3.5 mA at 24 V DC
-
-
Status display (LED): Green
-
Error monitoring: Internal function monitoring
-
External test clocking: Optional
Digital Outputs
-
Quantity: 8 digital outputs - can be used redundantly in pairs (PL e/SIL3/Cat 4)
-
Output voltage range: 18 .. 34 V DC
-
Output current per channel (max.): 0.5 A nominal
-
Total current per group (max.): 2 A
-
Delay 0 to 1: Max. 35 µs at full load
-
Delay 1 to 0: Max. 155 µs at full load
-
Output groups: 2, electronic fuse
-
Status display (LED): Green
-
Switching frequency (max., ohmic load): 500 Hz
-
Error monitoring: Short circuit, overload, inadequate or excess voltage of the power supply
-
Time-delayed emergency shut-off: Each output individual from 0 .. 1800 s configurable (resolution 100 ms)
-
Emergency shut-off activated in the event of: Communication loss (e.g., cable break or failure in the supply voltage)
-
Internal Power Supply
-
Galvanic isolation from the system: 500 V
-
Galvanic isolation between groups: 500 V
-
Internal power supply: Backplanes BS2xx
-
Current consumption internal: 5 V / 600 mA via backplane
External Power Supply
-
Reverse polarity protection: Yes
-
Input voltage: 24 V DC (18 .. 34 V)
-
Current consumption: Normally 95 mA at +24 VDC + Σ current consumption of the encoders and sensors
Connection Technology
-
Connection type: Screw or spring terminal, writable and codable plug
Standards
-
Machine safety: IEC61508: Functional safety – draft of complex E/E/PE safety components
-
Approved for:
-
ISO13849: Safety of Machinery
-
IEC62061: Functional safety machine-related E/E/PE systems
-
IEC61511: Functional safety equipment and process industry
-
EN954
-
-
Product standard: IEC61131-2
-
UL508
Additional Features
-
Status display via LEDs
-
Operating mode adjustable via hex switch
Ambient Conditions
Condition | Standard | ColdClimate (❉) |
---|---|---|
Operating temperature | -20 .. +60°C fanless | -30 .. +60°C fanless |
Relative humidity operation | 5 .. 95% without condensation | 5 .. 95% with condensation |
Storage temperature | -40 .. +85°C | -40 .. +85°C |
Relative humidity storage | 5 .. 95% without condensation | 5 .. 95% with condensation |
Model Variants
-
SLC284: Safety CPU module; integrated digital input/output; SIL3/PLe: 8x DI 24V; 4x DO 24V / 0.5A; (SIL2/PLd: 16x DI, 8x DO); 6ms cycle time; RS232; operating standalone or with CPU module
-
SLC284❉: Like SLC284; ColdClimate (❉)