Product Description
General Information
Manufacturer |
Honeywell |
---|---|
Model/Part Number |
CC-TAIN01 |
Description |
Analog Input Module |
Function
The Analog Input Module is designed to accept high-level current input from sensing devices.
Notable Features
• Extensive self-diagnostics
• Optional redundancy
• Supplies non-incendive field power
• Fast loop scan
Technical Specifications
Parameter |
Specification |
---|---|
Input/Output Model |
CC-PAIN01 - High-Level Analog Input |
IOTA Models |
CC-TAIN01 (Non-Redundant, 6”)CC-TAIN11 (Redundant, 12”) |
Input Type |
Current (2-wire or self-powered transmitters) |
Input Channels |
16 Channels (16 Single Ended) |
Common Mode Rejection Ratio (DC to 60 Hz, 500 Ω source imbalance) |
70 dB |
A/D Converter Resolution |
16 bits |
Input Range |
4-20 mA (through 200 Ω) |
Normal Mode Rejection Ratio (at 60 Hz) |
20 dB |
Normal Mode Filter Response |
Single-pole RC, -3 dB @ 6.0 Hz |
Maximum Normal Mode Input |
± 30 Volts |
Crosstalk (DC to 60 Hz, channel-to-channel) |
-60 dB |
Input Scan Rate |
50 ms |
Hardware Accuracy |
± 0.075% of full-scale (23.5°± 2°C) ± 0.15% of full-scale (0 to 60°C) |
Transmitter Field Power Conditioning |
Individually protected current limiting circuits for Class 1, Div 2 non-incendive interfacing. No fusing required. |