The Honeywell CC-PUIO01 51454205-175 Universal Input Output module is a versatile, safety-oriented I/O device designed for Honeywell’s Series C platform within the Experion Process Knowledge System (PKS) or Safety Manager systems. This module supports up to 32 channels, configurable for both analog and digital inputs/outputs with HART communication, offering flexibility for industrial automation applications. Featuring a 16-bit A/D converter for inputs, 12-bit resolution for outputs, and robust diagnostics (e.g., open wire detection), it ensures precise signal processing and reliable performance in demanding environments.
Technical Information
Parameter | Specifications |
---|---|
Manufacturer | Honeywell |
Model/Part Number | CC-PUIO01 51454205-175 |
Description | Universal Input Output |
Analog Input with HART | |
Input Type | Current (2, 3, or 4-wire devices) |
Input Channels | 32 maximum per module (with or without open wire detect) |
A/D Converter Resolution | 16-bit |
Input Range | 0-20 mA or 4-20 mA |
Normal Mode Rejection Ratio, at 60 Hz | 12 dB |
Normal Mode Filter Response | Single pole, -3 dB @ 16 Hz |
Crosstalk, DC to 60 Hz (channel-to-channel) | 60 dB |
Input Impedance | 250 Ω nominal |
Maximum Input Voltage (any input referenced to common, no damage) | +36 V DC to -1.1 V DC |
Input Scan Rate | 50 ms |
Hardware Accuracy | 0.1% of full scale (23.5 ± 2°C) 0.17% of full scale (-40 to +70°C) |
Transmitter Field Power Conditioning | Current limited to 24 mA |
Input Filter | First-order low-pass, 16 Hz |
Channels (Pulse Input Specific) | 15, 16, 17, 18 |
Frequency (Pulse Input) | 0-10 kHz |
Minimum Pulse Width | 50 µs |
Duty Cycle | Any duty cycle meeting the minimum pulse width specification |
Analog Output with HART | |
Output Type | 4-20 mA current loop |
Output Channels | 32 maximum per module (with or without open wire detect) |
Output Ripple | < 125 mV peak-to-peak at power line frequency, across 250 Ω load |
Output Temperature Drift | 0.001% of full scale/°C |
Output Readback Accuracy | 0.25% of full scale |
Output Current Linearity | ± 0.05% of full scale nominal |
Resolution | 12-bit |
Calibrated Accuracy | < 0.5% of full scale (25°C) including linearity |
Directly Settable Output Current Range | 0 mA to 23 mA |
Maximum Resistive Load (24 V supply = 22 V DC through 28 V DC) | 700 ohms |
Maximum Output Compliant Voltage (24 V supply = 22 V DC through 28 V DC) | 14 V DC |
Maximum Open Circuit Voltage | 24 V DC |
Response Time (DAC input code to output) | 2 ms |
Gap (0 mA) of Output to Field on Switchover | 0 ms (both partners continuously active) |
Digital Input (Contact Detection, First Set) | |
Open Voltage | 24 V DC |
Short Circuit Current | 7 mA |
Open Contact | 15 kΩ > 0.1 W |
Closed Contact | 5 kΩ > 0.25 W |
Closed Contact Detection | 1.8 mA < I < 6 mA |
Open Contact Detection | 0.7 mA < I < 1.8 mA |
Open Wire Detect | I < 0.7 mA |
Input Filter | First-order low-pass, 16 Hz |
Digital Input (Contact Detection, Second Set) | |
Open Voltage | 24 V DC |
Closed Contact Current | 7 mA ± 5% (after open state detection) 3.5 mA ± 5% (after closed state detection) |
Closed Contact Detection | I > 2.81 mA |
Open Contact Detection | I < 1.8 mA |
Input Filter | First-order low-pass, 16 Hz |