Product Description
🔍
Product Details
Field |
Details |
---|---|
Manufacturer |
Honeywell |
Model/Part Number |
2MLI-CPUU |
Description |
Central Processing Unit (CPU) module with power supply compatibility (AC/DC inputs) |
⚙️
Technical Specifications (Power Supply Options)
Item |
2MLP-ACF1 |
2MLP-ACF2 |
2MLP-AC23 |
2MLP-DC42 |
---|---|---|---|---|
Rated Input Voltage |
AC 100 – 240V |
AC 200 – 240V |
AC 200 – 240V |
DC 24V |
Input Voltage Range |
AC 85 – 264V |
AC 170 – 264V |
AC 170 – 264V |
— |
Input Frequency |
50/60 Hz (47 – 63 Hz) |
50/60 Hz (47 – 63 Hz) |
50/60 Hz (47 – 63 Hz) |
— |
Inrush Current |
≤ 20 A peak |
≤ 80 A peak |
≤ 80 A peak |
— |
Efficiency |
≥ 65% |
≥ 60% |
≥ 60% |
— |
Input Fuse |
Built-in, UL standard (slow-blow) |
Same |
Same |
Same |
Instant Interruption Tolerance |
≤ 10 ms |
Same |
Same |
Same |
⚡
Output Specifications
Output Channel |
Parameter |
Values |
---|---|---|
Output 1 |
Voltage |
5 VDC (±2%) |
Current |
3.0A / 6.0A / 8.5A / 6.0A (depending on power model) |
|
Overcurrent Protection |
Triggers ≥ 3.2A / 6.6A / 9.0A / 6.6A |
|
Overvoltage Protection |
5.5V to 6.5V |
|
Output 2 |
Voltage |
24 VDC (±10%) (only on 2MLP-DC42) |
Current |
0.6A |
|
Overcurrent Protection |
≥ 0.7A |
🔌
Relay Output Specs
Parameter |
Value |
---|---|
Application |
RUN Contact |
Rated Voltage/Current |
24V DC, 0.5A |
Minimum Load |
5V DC, 1 mA |
Response Time |
OFF→ON: ≤10 ms / ON→OFF: ≤12 ms |
Mechanical Life |
≥ 20 million operations |
Electrical Life |
≥ 100,000 operations |
Indicator |
Output Voltage Normal: LED ON |
📐
Mechanical and Electrical
Attribute |
Details |
---|---|
Cable Spec |
0.75 – 2 mm² |
Terminal Type |
RAV 1.25–3.5, RAV 2–3.5 |
Weight |
0.4 kg to 0.6 kg (varies by model) |