Manufacturer: BACHMANN
-
Model/Part Number: FS222/N
-
Description: FASTBUS Modules
General Information
The FASTBUS modules (FM221, FM222, FS221/N, FS222/N) are designed to enable the distribution of substations over long distances with very low signal delay. The FS222/N is a FASTBUS slave module with an integrated power supply, capable of supplying the I/O modules of a substation. The flexible connector concept allows easy connection via either a patch cable or an industrial-grade push-pull plug connection via an adapter.
Key Features:
- FASTBUS master modules with 1 or 2 FO interfaces
- FASTBUS slave modules with integrated power supply
- Supports up to 15 distributed substations
- Connection via robust Harting PushPull® connector or LC patch cable
- Transmission distances up to 2000 m via multimode fiber
- Minimal signal delay
-
ColdClimate models available
Order Codes
Model |
Order Code |
Description |
FS222/N |
00016749-00 |
FASTBUS slave with 2 FO ports, 50/62.5μm multimode fiber, up to 2000m, LC connector, integrated power supply 18.25W |
Integrated Power Supply
Attribute |
Specification |
Input Voltage |
24 VDC (18 to 34 V) |
Nominal Power (Output) |
18.25 W |
Output Current at +5 V |
3000 mA |
Output Current at +15 V |
250 mA |
Output Current at -15 V |
200 mA |
Ambient Conditions
Attribute |
Standard Model |
ColdClimate Model |
Operating Temperature |
-30 to +60 °C |
-30 to +60 °C |
Relative Humidity (Operation) |
5 to 95 % without condensation |
5 to 95 % with condensation |
Storage Temperature |
-40 to +85 °C |
-40 to +85 °C |
Relative Humidity (Storage) |
5 to 95 % with condensation |
5 to 95 % with condensation |
Pollution Degree |
2 (without condensation; according to IEC 60664-1) |
2 (according to IEC 60664-1) |
FASTBUS Interface
Attribute |
Specification |
Line Length |
2000 m between the stations, total length max. 2300 m |
Transmission Medium |
Multimode fiber (50/125 μm and 62.5/125 μm), max. 2000 m |
FOC Connector Type |
LC |
FOC Guide Wavelength |
1310 nm |
Number of Stations |
Max. 16 (max. 10 per line) |
Link Budget |
> 8 dB (3 dB reserve) |