Product Description
General Information
Manufacturer |
Emerson |
---|---|
Model/Part Number |
CON041+PR6424/006-131 |
Description |
Eddy Current Signal Converter with Sensor |
CON041 Eddy Current Signal Converter
Dynamic Performance
Parameter |
Value |
---|---|
Frequency Range (-3 dB) |
0 to 20,000 Hz |
Rise Time |
<15µs |
Supported Sensor Models |
PR6422, PR6423, PR6424, PR6425, PR6426 |
Extended Range Models |
CON041/91x-xxx (PR6425 requires extended range converter) |
Environmental Limits
Parameter |
Value |
---|---|
Operating Temperature Range |
-30 to 100°C (-22 to 212°F) |
Shock and Vibration |
5g @ 60Hz @ 25°C (77°F) |
Protection Class |
IP20 |
Power & Electrical
Parameter |
Value |
---|---|
Supply Voltage Range |
-23V to -32V (Output Range -4V to -20V) |
-21V to -32V (Output Range -2V to -18V) |
Physical Characteristics
Parameter |
Value |
---|---|
Housing Material |
PA 6.6 |
Weight |
~60 grams (2.12 oz) |
Mounting |
DIN Rail |
Connections |
Screw Terminal (Max. 1.5mm², Wire-end Sleeves) |
PR6424 Eddy Current Sensor (16mm)
Dynamic Performance
Parameter |
Value |
---|---|
Sensitivity/Linearity |
4 V/mm (101.6 mV/mil) ≤ ±1.5% |
Air Gap (Center) |
Approx. 2.7 mm (0.11”) Nominal |
Long Term Drift |
<0.3% |
Static Range |
±2.0 mm (0.079”) |
Dynamic Range |
0 to 1,000μm (0 to 0.039”) |
Target Specifications
Parameter |
Value |
---|---|
Target Material |
Ferromagnetic Steel (42CrMo4 Standard) |
Maximum Surface Speed |
2,500 m/s (98,425 ips) |
Minimum Shaft Diameter |
≥80mm |
Environmental Limits
Parameter |
Value |
---|---|
Operating Temperature Range |
-35 to 150°C (-31 to 302°F) |
Temperature Error |
<4%/100°K (API 670 Compliant) |
Pressure Resistance (Sensor Head) |
10,000 hPa (145 psi) |
Shock and Vibration |
5g @ 60Hz @ 25°C (77°F) |
Physical Characteristics
Parameter |
Value |
---|---|
Sleeve Material |
Stainless Steel |
Cable Material |
PTFE |
Weight (Sensor & 1m Cable, No Armor) |
~200 grams (7.05 oz) |
Ordering Information
CON041 Signal Converter
Model Number |
Sensor Type |
Measuring Range |
Linearity Error |
---|---|---|---|
CON041 |
PR6422, PR6423, PR6424, PR6426 |
1.0mm - 8.0mm (Standard Range) |
≤1.0% - ≤1.5% |
CON041/914-060 |
PR6424 |
6.0mm (Extended Range) |
≤1.0% |
CON041/914-080 |
PR6424 |
8.0mm (Extended Range) |
≤1.5% |
CON041/914-100 |
PR6424 |
10.0mm (Extended Range) |
≤2.0% |
PR6424 Sensor Order Matrix
Parameter |
Options |
---|---|
Sleeve Thread |
M18x1.5 (0), 3/4”-16 UNF (1) |
Armored Cable |
With (1), Without (0) |
Total Sensor Length |
40mm (0), 50mm (1), 60mm (2), 70mm (3), 80mm (4), 90mm (5), 100mm (6), 150mm (B), 200mm (G), 250mm (M), 290mm (R) |
Adapter Plug |
With (0), Without (1) |
Total Cable Length |
4m (0), 5m (1), 8m (3), 10m (4) |
Cable End |
LEMO (0), Open (1) |