Product Description
Product Details
Manufacturer |
Bently Nevada |
Series |
3500/92 |
Model/Part Number |
3500/92-04-01-00 |
Model Type |
Communication Gateway |
Description
The 3500/92 Communication Gateway module offers extensive communication capabilities for integrating all monitored values and statuses with process control and automation systems. It supports both Ethernet TCP/IP and serial (RS232/RS422/RS485) communication protocols. Additionally, it facilitates Ethernet communication with 3500 Rack Configuration Software and Data Acquisition Software.
Specifications
Parameter |
Value |
Power Consumption |
5.0 Watts typical with Modbus RS232/RS422 I/O Module |
|
5.6 Watts typical with Modbus RS485 I/O Module |
Data Types Collected |
Current measured values with time stamp, module statuses, and alarm statuses from other modules in the rack |
Data Collection Rate |
Update time not exceeding 1 second for all modules in the 3500 rack |
LED Indicators |
OK LED: Indicates proper operation |
|
TX/RX LED: Indicates communication activity |
Inputs |
Internal high-speed network communication with other modules in the rack |
Outputs |
Status and alarm data returned for each module |
Physical Dimensions
Module Type |
Dimensions (HxWxD) |
Weight |
Main Board |
241 mm x 24.4 mm x 242 mm |
0.82 kg (1.8 lb) |
I/O Modules |
241 mm x 24.4 mm x 99.1 mm |
0.44 kg (0.96 lb) |
Environmental Limits
Parameter |
Value |
Operating Temperature |
-30°C to +65°C (-22°F to +149°F) |
Storage Temperature |
-40°C to +85°C (-40°F to +185°F) |
Humidity |
95%, non-condensing |
Ordering Information
Parameter |
Option |
I/O Module Type |
01: Modbus RS232/RS422 I/O Module |
|
02: Modbus RS485 I/O Module |
|
03: Ethernet/RS232 Modbus I/O Module |
|
04: Ethernet/RS485 Modbus I/O Module |
Memory Type |
01: Low Memory |
Agency Approval Option |
00: None |
|
01: CSA/NRTL/C |
|
02: CSA/ATEX/IECEx |
Download PDF file here: