Product Description
Product Details
Manufacturer: Allen-Bradley
Model/Part Number: PLC5 1771-OM
Description: AC Output Module
Specifications
Attribute | Details |
---|---|
Outputs per Module | 16 (8 outputs per group, 2 groups) |
Module Location | 1771 I/O Chassis |
Output Voltage Range | 184 to 250V AC, 47-63Hz |
Output Current Rating | 2A per output, not to exceed 6A per module |
Surge Current (maximum) | 20A for 100ms, repeatable every 10 seconds |
Load Current (minimum) | 60mA per output @ 220V AC, 60Hz |
On-State Voltage Drop (max.) | 1.6V at 2A |
Off-State Leakage Current (max.) | 2mA per output @ 220V AC |
Signal Delay | Off to On: 1.0ms On to Off: 8.3ms @ 60Hz (max) |
Power Dissipation | 13.2 Watts (Max); 1.2 Watts (Min.) per module |
Thermal Dissipation | 45.1 BTU/hr (Max); 4.1 BTU/hr (Min.) |
Backplane Current | 225mA @ 5V DC ±5% |
Isolation Voltage | Meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142 |
Environmental Conditions | |
Operating Temperature | 0°C to 60°C (32°F to 140°F) |
Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
Relative Humidity | 5% to 95% (without condensation) |
Conductors | 14 gauge (2mm) stranded maximum |
Wire Size | 3/64 inch (1.2mm) insulation maximum |
Category | 2 |
Fuses | 2A, 250V 3AG Normal Blow (1 per output), Buss Fuse AGC-2, Littelfuse 312002 |
Field Wiring Arm | Catalog Number 1771-WA |
Wiring Arm Screw Torque | 7–9 inch-pounds |
Certifications | CSA Certified CSA Class I, Division 2 (Groups A, B, C, D) Certified UL Listed CE Marked (complies with applicable directives) |
Installation Instructions | Refer to manual 1771-2.18 |