Product Description
Product Details
Manufacturer: Allen-Bradley
Model/Part Number: PLC5 1771-OD16
Description: Isolated AC Output Module
Specifications
Attribute | Details |
---|---|
Outputs per Module | 16 (8 outputs per group, 2 groups) |
Module Location | 1771-A1B thru -A4B or later I/O Chassis |
Voltage Rating | 74 to 138V AC, 47-63Hz |
Current Rating (per channel) | 5mA to 2A continuous (max); 20A surge for 100ms; repeatable every 2 seconds |
Power Rating | 3 Watts per output (Max) @ 2A |
On-state Voltage Drop (each output) | 5.7V RMS (max) @ load current < 70mA; 1.5V RMS (max) @ load current > 70mA |
On-state Load Current | 5mA minimum |
Off-state Leakage Current | 3.0mA max. @ 138V AC; 1.5mA (typical) @ 120V AC |
Zero Voltage Turn-on | 25V AC maximum; 15V AC typical |
Signal Delay Times | Off to On: 8.8ms @ 60Hz (max), 10.6ms @ 50Hz (max) On to Off: 8.8ms @ 60Hz (max), 10.6ms @ 50Hz (max, zero cross switching) |
Power Dissipation | 13.0 Watts (Max); 1.0 Watts (Min.) |
Thermal Dissipation | 44.4 BTU/hr (Max); 3.4 BTU/hr (Min.) |
Backplane Current | 200mA max. |
Isolation Voltage | Meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142 |
Maximum Cable Length | 1000 ft (304.8 m) |
Operating Temperature | 0°C to 60°C (32°F to 140°F) |
Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
Relative Humidity | 5% to 95% (without condensation) |
Wire Size | 14 gauge (2mm) stranded maximum |
Insulation | 3/64 inch (1.2mm) maximum |
Category | 1 |
Fuses | 3A 2AG Slo-Blo fuses (1 per output), Littelfuse P/N 229003 Optional Fuse Kit |
Field Wiring Arm | Catalog Number 1771-WN |
Wiring Arm Screw Torque | 7–9 inch-pounds |
Certifications | CSA Certified CSA Class I, Division 2 (Groups A, B, C, D) Certified UL Listed CE Marked (complies with applicable directives) |
Installation Instructions | Refer to manual 1771-5.21 |