Product Description
Product Details
Manufacturer: Allen-Bradley
Model/Part Number: 1788-DNBO
Description: FlexLogix DeviceNet Daughtercard
Specifications
Characteristic | Value |
---|---|
Power Requirements | Host: 5V DC @ 260mA DeviceNet: 24V DC @ 20mA (Class 2) |
Power Consumption | 5V DC: 1.3W 24V DC: 0.48W Total: 1.78W |
Thermal Dissipation | 6.1 BTU/hr |
Isolation Voltage | Tested to withstand 707V DC for 60 seconds |
RTB Screw Torque | 5-7 inch-pounds (0.56-0.8 Nm) |
Conductors Wire Size | 24-12 AWG (0.205-3.31 mm²) stranded copper 3/64 inch (1.2mm) insulation maximum |
Wiring Category | Category 2 (on communications ports) |
Emissions | CISPR 11: Group 1, Class A (with appropriate enclosure) |
ESD Immunity | IEC 61000-4-2: 6kV contact discharges 8kV air discharges |
Radiated RF Immunity | IEC 61000-4-3: 10V/m with 1kHz sine-wave 80% AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100% AM at 900MHz |
EFT/B Immunity | IEC 61000-4-4: ±2kV at 5kHz on communications ports |
Surge Transient Immunity | IEC 61000-4-5: +2kV line-earth (CM) on shielded ports |
Conducted RF Immunity | IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80% AM from 150kHz to 80MHz |
Enclosure Type Rating | None (open-style) |
Operating Temperature | IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 60°C (32 to 140°F). Acceptable for the ambient slot temperature immediately surrounding this product to reach 85°C (185°F). |
Storage Temperature | IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85°C (–40 to 185°F). |
Relative Humidity | IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing |
Shock | IEC 60068-2-27 (Test Ea, Unpackaged Shock): Operating 30g Non-operating 50g |
Vibration | IEC 60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz |
Weight | 0.1 kg (0.2 lb) |
Certifications
-
c-UR-us: UL Recognized Component Industrial Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for US and Canada. -
CE: Compliant with European Union 89/336/EEC EMC Directive, with conformance to:
- EN 50081-2 (Industrial Emissions)
- EN 50082-2 (Industrial Immunity)
- EN 61326 (Meas./Control/Lab., Industrial Requirements)
- EN 61000-6-2 (Industrial Immunity)
- C-Tick: Compliant with the Australian Radiocommunications Act, AS/NZS 2064 (Industrial Emissions).
- ODVA: ODVA conformance tested to DeviceNet specifications.