Product Description
Technical Specifications
Power & Electrical Characteristics
Attribute | Value |
---|---|
Max Power Consumption | 16.8 W |
Max Power Dissipation | 8.8 W |
Max Input Current | 700 mA @ 24V DC SELV |
Input Voltage Range | 18–36V DC |
Max Backplane Output Current | 1.6A @ 5V DC |
Physical & Wiring
Attribute | Value |
---|---|
Wire Size | 0.21–3.3 mm² (24–12 AWG) |
Max Insulation Thickness | 1.2 mm (3/64 in.) |
Wiring Category | 2 (Power Ports & ControlNet Ports) |
Terminal Block Torque | 0.6–0.8 N•m (5.3–7.1 lb•in.) |
Safety & Isolation
Attribute | Value |
---|---|
Isolation Voltage | SELV (Functional Insulation, ControlNet to System) |
Enclosure Type | None (Open-Style Module) |
Temperature Rating (North America, IECEx, ATEX) | T5 |
Environmental Specifications
Environmental Condition | Value |
---|---|
Operating Temperature | 0 to 60°C (32 to 140°F) |
Max Ambient Temperature | 60°C (140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Relative Humidity | 5–95% (Non-condensing) |
Mechanical Resistance
Test Type | Test Standard | Value |
---|---|---|
Vibration | IEC 60068-2-6 | 5g @ 10–500 Hz |
Shock (Operating) | IEC 60068-2-27 | 30g |
Shock (Non-operating) | IEC 60068-2-27 | 50g |
Electromagnetic Compatibility (EMC) & Interference Immunity
Immunity Type | Test Standard | Value |
---|---|---|
Electrostatic Discharge (ESD) Immunity | IEC 61000-4-2 | 6kV Contact Discharge, 8kV Air Discharge |
Radiated RF Immunity | IEC 61000-4-3 | 10V/m (80–2000 MHz) |
Electrical Fast Transient (EFT) Immunity | IEC 61000-4-4 | ±4 kV @ 5 kHz (Power & ControlNet Ports) |
Surge Immunity | IEC 61000-4-5 | ±1 kV Line-to-Line (DM), ±2 kV Line-to-Ground (CM) |
Conducted RF Immunity | IEC 61000-4-6 | 10V rms (150 kHz–80 MHz) |