Communication Ports |
(1) RS-232 |
(2) RS-232 |
User Memory |
64K bytes |
256K bytes |
Maximum Number of I/O Modules Supported |
8 I/O modules |
16 I/O modules |
Maximum Number of I/O Banks Supported |
2 banks |
3 banks |
Backplane Current |
600 mA at +5V dc, 0 mA at +24V dc |
800 mA at +5V dc, 0 mA at +24V dc |
Operating Temperature |
0° to +60°C (+32° to +140°F) |
0° to +60°C (+32° to +140°F) |
Storage Temperature |
-40° to +85°C (-40° to +185°F) |
-40° to +85°C (-40° to +185°F) |
Relative Humidity |
5% to 95% non-condensing |
5% to 95% non-condensing |
Power Supply Distance Rating |
4 (must be within four slot positions) |
4 (must be within four slot positions) |
Vibration |
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak |
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak |
Shock |
Operating: 30G, 11 ms, panel mounted (20G, 11 ms, DIN rail mounted) |
Operating: 30G, 11 ms, panel mounted (20G, 11 ms, DIN rail mounted) |
Non-operating Shock |
40G, panel mounted (30G, DIN rail mounted) |
40G, panel mounted (30G, DIN rail mounted) |
Shipping Weight |
325g (0.715 lbs) |
360g (0.792 lbs) |
Battery |
1747-BA, containing Sanyo CR14250SE battery cell |
1747-BA, containing Sanyo CR14250SE battery cell |
Programming Cable |
1747-CP3 or 1756-CP3 |
1747-CP3 or 1756-CP3 |
Agency Certification |
C-UL certified (under CSA C22.2 No.142), UL 508 listed, CE compliant |
C-UL certified (under CSA C22.2 No.142), UL 508 listed, CE compliant |
Hazardous Environment Class |
Class I, Division 2, Hazardous Location, Groups A, B, C, D |
Class I, Division 2, Hazardous Location, Groups A, B, C, D |
Radiated and Conducted Emissions |
EN50081-2 Class A |
EN50081-2 Class A |
Electrical / EMC Immunity |
|
|
ESD Immunity |
IEC61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect |
IEC61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect |
Radiated Immunity |
IEC61000-4-3, 10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier |
IEC61000-4-3, 10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier |
Fast Transient Burst |
IEC61000-4-4, 2 kV, 5 kHz |
IEC61000-4-4, 2 kV, 5 kHz |
Surge Immunity |
IEC61000-4-5, 1 kV galvanic gun |
IEC61000-4-5, 1 kV galvanic gun |
Conducted Immunity |
IEC61000-4-6, 10V, 0.15 to 80 MHz |
IEC61000-4-6, 10V, 0.15 to 80 MHz |