Skip to product information
1 of 3

Allen-Bradley 1768-PA3 CompactLogix L4x AC/DC In Power Supply

Allen-Bradley 1768-PA3 CompactLogix L4x AC/DC In Power Supply

  • Manufacturer: Allen-Bradley

  • Product No.: 1768-PA3

  • Condition:1000 in stock

  • Product Type: CompactLogix L4x AC/DC In Power Supply

  • Product Origin: USA

  • Payment: T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

  • 24/7 Support
  • 30-Day Returns
  • Fast Shipping

Product Details: Allen-Bradley CompactLogix L4x AC/DC In Power Supply (Model: 1768-PA3)


General Overview

  • Manufacturer: Allen-Bradley
  • Model/Part Number: 1768-PA3
  • Description: The CompactLogix L4x AC/DC In Power Supply 1768-PA3 is designed for providing reliable power to the CompactLogix controller and other connected components. It supports both AC and DC input voltages, offering versatility for various industrial applications.

Specifications

Attribute 1768-PA3 1768-PB3
Efficiency 75% Typical 80% Typical @ 24V dc
Enclosure Type Rating None (open-style) None (open-style)
Input Voltage Range 85…265V ac, 108…132V dc, 16.8-31.2V dc 85…265V ac, 108…132V dc, 16.8-31.2V dc
Input Frequency Range 47…63 Hz (85…265V ac) N/A
Input Power, Max 120 VA/120 W 112 W @ 24V dc
Inrush Current, Nominal 25 A @ 85…132V ac, 50 A @ 195…265V ac, 25 A @ 108…132V dc 50 A @ 195…265V ac, 25 A @ 108…132V dc, 30 A @ 16.8…31.2V dc
Inrush Current, Max 50 A @ 85…132V ac 80 A @ 195…265V ac, 50 A @ 16.8…31.2V dc
North American Temp Code T4 T5
Power Dissipation, Max 30 W 22 W @ 24V dc
Isolation Voltage 250V (Reinforced Insulation Type) 250V (Reinforced Insulation Type)
Internal Overcurrent Protection Non-replaceable fuse (soldered in place) Non-replaceable fuse (soldered in place)
Recommended External Overcurrent Protection 4…6 A @ 28.5…36.7 A2 S, 8...12 A @ 166...250 A2S 8…12 A @ 166…250 A2S
Overcurrent Protection, Max 15 A (user supplied) 15 A (user supplied)
Wire Size (Input Power Terminal) 14 AWG (2.5 mm²), solid or stranded copper wire (75°C or greater) 14 AWG (2.5 mm²), solid or stranded copper wire (75°C or greater)
Wire Size (Output Power Terminal) 2.5 mm² (14 AWG) to 0.25 mm² (22 AWG) solid or stranded wire 2.5 mm² (14 AWG) to 0.25 mm² (22 AWG) solid or stranded wire
Conductor Screw Torque 0.6 Nm (5 lb-in) 0.6 Nm (5 lb-in)
Dimensions (HxWxD) 131.25 x 132.75 x 105.50 mm (5.17 x 5.23 x 4.15 in.) 131.25 x 132.75 x 105.50 mm (5.17 x 5.23 x 4.15 in.)
Weight 0.98 kg (2.15 lb) 1.01 kg (2.22 lb)
Continuous Output Power 90 W, Max 90 W, Max
Continuous Output Power (Min) 6 W, Min 6 W, Min
Output #1 (24V dc to Backplane) 3.5 A 3.5 A
Output #2 (24V dc to Front Panel Terminal Block) 0.25 A 0.25 A
Ride-through Interval Time (Min) 25 ms @ 90 W 5 ms @ 90 W
Full Power Hold-up Interval 5 ms @ 90 W 5 ms @ 90 W
Extended Hold-up Interval 8…12 s @ 1.25 W 8…12 s @ 1.25 W
Output Disable Disable output during hold-up periods Disable output during hold-up periods

Environmental Specifications

Attribute 1768-PA3 1768-PB3
Conducted RF Immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave, 80% AM from 150 kHz…80 MHz IEC 61000-4-6: 10V rms with 1 kHz sine-wave, 80% AM from 150 kHz…80 MHz
EFT/B Immunity IEC 61000-4-4: ±4kV at 5 kHz on power ports IEC 61000-4-4: ±4kV at 5 kHz on power ports
Emissions CISPR 11: Group 1, Class A CISPR 11: Group 1, Class A
ESD Immunity IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
Radiated RF Immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz
Relative Humidity IEC 60068-2-30: 5…95% noncondensing IEC 60068-2-30: 5…95% noncondensing
Shock (Operating) IEC 60068-2-27: 30 g IEC 60068-2-27: 30 g
Shock (Non-operating) IEC 60068-2-27: 50 g IEC 60068-2-27: 50 g
Surge Transient Immunity IEC 61000-4-5: ±2 kV line-line, ±4 kV line-earth on ac power ports IEC 61000-4-5: ±2 kV line-line, ±4 kV line-earth on ac power ports
Temperature (Operating) IEC 60068-2-1: 0…60 °C (32…140 °F) IEC 60068-2-1: 0…60 °C (32…140 °F)
Temperature (Storage) IEC 60068-2-2: -40…85 °C (-40…185 °F) IEC 60068-2-2: -40…85 °C (-40…185 °F)
Vibration IEC 60068-2-6: 5 g @ 10…500 Hz IEC 60068-2-6: 5 g @ 10…500 Hz
Voltage Variation IEC 61000-4-11, IEC 61000-4-29: ±10% fluctuations, 30% dips, 60% dips, interruptions on ac and dc supply ports IEC 61000-4-11, IEC 61000-4-29: ±10% fluctuations, 30% dips, 60% dips, interruptions on ac and dc supply ports

Certifications

Certification Details
C-Tick Australian Radio Communications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
UL Certification UL Listed Industrial Control Equipment for US and Canada. UL File E65584.
Hazardous Location Certification UL Listed for Class I, Division 2, Groups A, B, C, D, Hazardous Locations (US & Canada). UL File E194810.
CE Certification Compliant with EU EMC Directive 2004/108/IEC and
View full details

Product Description

Product Details: Allen-Bradley CompactLogix L4x AC/DC In Power Supply (Model: 1768-PA3)


General Overview

  • Manufacturer: Allen-Bradley
  • Model/Part Number: 1768-PA3
  • Description: The CompactLogix L4x AC/DC In Power Supply 1768-PA3 is designed for providing reliable power to the CompactLogix controller and other connected components. It supports both AC and DC input voltages, offering versatility for various industrial applications.

Specifications

Attribute 1768-PA3 1768-PB3
Efficiency 75% Typical 80% Typical @ 24V dc
Enclosure Type Rating None (open-style) None (open-style)
Input Voltage Range 85…265V ac, 108…132V dc, 16.8-31.2V dc 85…265V ac, 108…132V dc, 16.8-31.2V dc
Input Frequency Range 47…63 Hz (85…265V ac) N/A
Input Power, Max 120 VA/120 W 112 W @ 24V dc
Inrush Current, Nominal 25 A @ 85…132V ac, 50 A @ 195…265V ac, 25 A @ 108…132V dc 50 A @ 195…265V ac, 25 A @ 108…132V dc, 30 A @ 16.8…31.2V dc
Inrush Current, Max 50 A @ 85…132V ac 80 A @ 195…265V ac, 50 A @ 16.8…31.2V dc
North American Temp Code T4 T5
Power Dissipation, Max 30 W 22 W @ 24V dc
Isolation Voltage 250V (Reinforced Insulation Type) 250V (Reinforced Insulation Type)
Internal Overcurrent Protection Non-replaceable fuse (soldered in place) Non-replaceable fuse (soldered in place)
Recommended External Overcurrent Protection 4…6 A @ 28.5…36.7 A2 S, 8...12 A @ 166...250 A2S 8…12 A @ 166…250 A2S
Overcurrent Protection, Max 15 A (user supplied) 15 A (user supplied)
Wire Size (Input Power Terminal) 14 AWG (2.5 mm²), solid or stranded copper wire (75°C or greater) 14 AWG (2.5 mm²), solid or stranded copper wire (75°C or greater)
Wire Size (Output Power Terminal) 2.5 mm² (14 AWG) to 0.25 mm² (22 AWG) solid or stranded wire 2.5 mm² (14 AWG) to 0.25 mm² (22 AWG) solid or stranded wire
Conductor Screw Torque 0.6 Nm (5 lb-in) 0.6 Nm (5 lb-in)
Dimensions (HxWxD) 131.25 x 132.75 x 105.50 mm (5.17 x 5.23 x 4.15 in.) 131.25 x 132.75 x 105.50 mm (5.17 x 5.23 x 4.15 in.)
Weight 0.98 kg (2.15 lb) 1.01 kg (2.22 lb)
Continuous Output Power 90 W, Max 90 W, Max
Continuous Output Power (Min) 6 W, Min 6 W, Min
Output #1 (24V dc to Backplane) 3.5 A 3.5 A
Output #2 (24V dc to Front Panel Terminal Block) 0.25 A 0.25 A
Ride-through Interval Time (Min) 25 ms @ 90 W 5 ms @ 90 W
Full Power Hold-up Interval 5 ms @ 90 W 5 ms @ 90 W
Extended Hold-up Interval 8…12 s @ 1.25 W 8…12 s @ 1.25 W
Output Disable Disable output during hold-up periods Disable output during hold-up periods

Environmental Specifications

Attribute 1768-PA3 1768-PB3
Conducted RF Immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave, 80% AM from 150 kHz…80 MHz IEC 61000-4-6: 10V rms with 1 kHz sine-wave, 80% AM from 150 kHz…80 MHz
EFT/B Immunity IEC 61000-4-4: ±4kV at 5 kHz on power ports IEC 61000-4-4: ±4kV at 5 kHz on power ports
Emissions CISPR 11: Group 1, Class A CISPR 11: Group 1, Class A
ESD Immunity IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
Radiated RF Immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz
Relative Humidity IEC 60068-2-30: 5…95% noncondensing IEC 60068-2-30: 5…95% noncondensing
Shock (Operating) IEC 60068-2-27: 30 g IEC 60068-2-27: 30 g
Shock (Non-operating) IEC 60068-2-27: 50 g IEC 60068-2-27: 50 g
Surge Transient Immunity IEC 61000-4-5: ±2 kV line-line, ±4 kV line-earth on ac power ports IEC 61000-4-5: ±2 kV line-line, ±4 kV line-earth on ac power ports
Temperature (Operating) IEC 60068-2-1: 0…60 °C (32…140 °F) IEC 60068-2-1: 0…60 °C (32…140 °F)
Temperature (Storage) IEC 60068-2-2: -40…85 °C (-40…185 °F) IEC 60068-2-2: -40…85 °C (-40…185 °F)
Vibration IEC 60068-2-6: 5 g @ 10…500 Hz IEC 60068-2-6: 5 g @ 10…500 Hz
Voltage Variation IEC 61000-4-11, IEC 61000-4-29: ±10% fluctuations, 30% dips, 60% dips, interruptions on ac and dc supply ports IEC 61000-4-11, IEC 61000-4-29: ±10% fluctuations, 30% dips, 60% dips, interruptions on ac and dc supply ports

Certifications

Certification Details
C-Tick Australian Radio Communications Act, compliant with AS/NZS CISPR 11; Industrial Emissions
UL Certification UL Listed Industrial Control Equipment for US and Canada. UL File E65584.
Hazardous Location Certification UL Listed for Class I, Division 2, Groups A, B, C, D, Hazardous Locations (US & Canada). UL File E194810.
CE Certification Compliant with EU EMC Directive 2004/108/IEC and

Download PDF file here:

Click to Download PDF