Product Description
Product Details
- Manufacturer: Allen-Bradley
- Model/Part Number: 1768-EWEB
- Description: EtherNet/IP Web Server Module
Technical Specifications
Attribute | 1768-ENBT | 1768-EWEB |
---|---|---|
EtherNet/IP Communication Rate | 10/100 Mbps | 10/100 Mbps |
Logix Communication Connections | 128 | 128 |
TCP/IP Communication Connections | 64 | 96 |
Current Draw @ 5V DC | N/A | 500 mA |
Current Draw @ 5.2V DC | 834 mA | N/A |
Current Draw @ 24V DC | 0 mA | N/A |
Power Consumption | 4.34 W | N/A |
Power Dissipation | 4.38 W | N/A |
Isolation Voltage | 30V (continuous), functional insulation type, Ethernet to system, tested at 710V DC for 60s | 50V (continuous), basic insulation type, tested at 710V DC for 60s |
Weight | 0.213 kg (7.5 oz) | 0.280 kg (0.61 lb) |
Dimensions (HxWxD) | 132 x 56.7 x 105.1 mm (5.20 x 2.23 x 4.12 in.) | 118 x 50 x 87 mm (4.65 x 1.97 x 3.43 in.) |
Slot Width | 1 | 1 |
Module Location | DIN rail or panel mount | DIN rail or panel mount |
Mounting Screw Torque | 1.16 N·m (10 lb·in) - use M4 or #8 screws | 1.16 N·m (10 lb·in) - use M4 or #8 screws |
Ports | 1 Ethernet RJ45 Category 5 | 2 Ethernet RJ45 Category 5 |
Wire Size | Ethernet connections: RJ45 connector according to IEC 60603-7, Category 5e or 5 cable | Ethernet connections: RJ45 connector according to IEC 60603-7, Category 5e or 5 cable |
Wire Category | 2 - on communication ports | 1 - on communication ports |
North American Temperature Code | T4A | T3C |
Enclosure Type Rating | None (open-style) | None (open-style) |
Certifications
Certification | 1768-ENBT & 1768-EWEB | 1769-AENTR |
---|---|---|
c-UL-us | UL Listed for US and Canada. See UL File E65584 | UL Listed for US and Canada. See UL File E322657 |
CE | Compliant with European Union EMC Directive | Compliant with European Union EMC Directive |
RCM | Compliant with Australian Radiocommunications Act | Compliant with Australian Radiocommunications Act |
Ex | Compliant with ATEX Directive: EN 60079-15, II 3 G Ex nA IIC T4 X | N/A |
EtherNet/IP | ODVA conformance tested to EtherNet/IP specifications | ODVA conformance tested to EtherNet/IP specifications |
Environmental Specifications
Attribute | 1768-ENBT | 1768-EWEB | 1768-CNB | 1768-CNBR |
---|---|---|---|---|
Operating Temperature | 0…60 °C (32…140 °F) | 0…60 °C (32…140 °F) | 0…60 °C | 0…60 °C |
Surrounding Air Temperature Max | 60 °C (140 °F) | 60 °C (140 °F) | 60 °C | 60 °C |
Non-Operating Temperature | -40…85 °C (-40…185 °F) | -40…85 °C (-40…185 °F) | -40…85 °C | -40…85 °C |
Relative Humidity | 5…95% noncondensing | 5…95% noncondensing | 5…95% | 5…95% |
Vibration (Operating) | 5 g @ 10…500 Hz | 5 g @ 10…500 Hz | 5 g @ 10…500 Hz | 5 g @ 10…500 Hz |
Shock (Operating) | 30 g | 30 g | 30 g | 30 g |
Shock (Non-Operating) | 50 g | 50 g | 50 g | 50 g |
Emissions | CISPR 11 (IEC 61000-6-4): Group 1, Class A | CISPR 11 (IEC 61000-6-4): Class A | CISPR 11 (IEC 61000-6-4): Group 1, Class A | CISPR 11 (IEC 61000-6-4): Class A |
ESD Immunity | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
Radiated RF Immunity | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz |
EFT/B Immunity | IEC 61000-4-4: ±2kV at 5 kHz on communication ports | IEC 61000-4-4: ±2kV at 5 kHz on communication ports | IEC 61000-4-4: ±2kV at 5 kHz on communication ports | IEC 61000-4-4: ±2kV at 5 kHz on communication ports |
Surge Transient Immunity | IEC 61000-4-5: ±2 kV line-earth (CM) on communication ports | IEC 61000-4-5: ±2 kV line-earth (CM) on communication ports | IEC 61000-4-5: ±2 kV line-earth (CM) on communication ports | IEC 61000-4-5: ±2 kV line-earth (CM) on communication ports |
Conducted RF Immunity | IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz | IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz | IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz | IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz |