🔹 General Information

Manufacturer

Allen-Bradley

Model/Part Number

1746-OW16/C

Description

16-Point Relay Output Module

Product Series

SLC 500


 



🔹 Specifications


Electrical Specifications

Attribute

Specification

Voltage Category

Relay Contact Output

Number of Outputs

16

Points per Common

8

Operating Voltage Range

5…125V DC / 5…265V AC

Backplane Current Consumption (5V DC)

0.255 A

Backplane Current Consumption (24V DC)

0.0 A

Signal Delay (Max. Resistive Load)

On = 10 ms, Off = 10 ms

Off-State Leakage (Max.)

None (mechanical relay contacts)

Load Current (Min.)

10 mA

Continuous Current per Point

2.5 A

Continuous Current per Module

8.0 A

Contact Ratings (Resistive Load)

2.5 A @ 120V AC, 2.5 A @ 240V AC, 2.0 A @ 125V DC

Surge Current per Point

5.0 A for 10 ms

Expected Contact Life (Min.)

100,000 operations at rated load


 

View full details

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)

Product Description

🔹 General Information

Manufacturer

Allen-Bradley

Model/Part Number

1746-OW16/C

Description

16-Point Relay Output Module

Product Series

SLC 500


 



🔹 Specifications


Electrical Specifications

Attribute

Specification

Voltage Category

Relay Contact Output

Number of Outputs

16

Points per Common

8

Operating Voltage Range

5…125V DC / 5…265V AC

Backplane Current Consumption (5V DC)

0.255 A

Backplane Current Consumption (24V DC)

0.0 A

Signal Delay (Max. Resistive Load)

On = 10 ms, Off = 10 ms

Off-State Leakage (Max.)

None (mechanical relay contacts)

Load Current (Min.)

10 mA

Continuous Current per Point

2.5 A

Continuous Current per Module

8.0 A

Contact Ratings (Resistive Load)

2.5 A @ 120V AC, 2.5 A @ 240V AC, 2.0 A @ 125V DC

Surge Current per Point

5.0 A for 10 ms

Expected Contact Life (Min.)

100,000 operations at rated load


 