Product Description
🔹 General Information
Manufacturer |
Allen-Bradley |
---|---|
Model/Part Number |
1734-FPD |
Description |
Power Distribution Module for POINT I/O Systems |
🔹 General Specifications
Attribute |
Value |
---|---|
Connect Terminal |
L1: 6 L2/N: 4 Chassis Ground: 2 |
Module Location |
Between I/O modules in the POINT I/O system |
Function |
Breaks power bus |
Indicators |
None |
POINTBus™ Current |
Pass through |
Power Consumption |
None |
Power Dissipation |
None |
Thermal Dissipation |
None |
Isolation Voltage |
50V continuous Tested @ 2600V DC for 60 s |
Input Voltage Rating |
12V DC, 24V DC (Nominal) 10…28.8V DC (Range) 120V AC, 240V AC (Nominal) |
Input Current (Max) |
10 A |
Field Power Bus Supply Voltage |
12V DC, 24V DC, 10…28.8V DC (Range) 120V AC, 240V AC, 50/60 Hz (1) (1) Ex compliance when used at or below 120V AC |
Field Power Bus Supply Current (Max) |
10 A |
Terminal Base Screw Torque |
0.6 N•m (7 lb•in) |
Dimensions (HxWxD), Approx. |
76.2 x 25.4 x 133.4 mm (3.00 x 1.00 x 5.25 in.) |
Weight, Approx. |
0.12 kg (0.27 lb) |
Wiring Category |
1 – on power ports |
Wire Size |
0.25…2.5 mm² (24…14 AWG) solid or stranded copper wire rated at 75°C (167°F) or greater, 1.2 mm (3/64 in.) insulation max |
Enclosure Type Rating |
None (Open-Style) |
🔹 Environmental Specifications
Attribute |
Value |
---|---|
Operating Temperature |
-20 °C…+55 °C (-4 °F…+131 °F) IEC 60068-2-1 (Cold), IEC 60068-2-2 (Dry Heat), IEC 60068-2-14 (Thermal Shock) |
Max Surrounding Air Temperature |
55 °C (131 °F) |
Non-Operating Temperature |
-40…+85 °C (-40…+185 °F) IEC 60068-2-1 (Cold), IEC 60068-2-2 (Dry Heat), IEC 60068-2-14 (Thermal Shock) |
Relative Humidity |
5…95% non-condensing IEC 60068-2-30 (Damp Heat) |
Vibration |
5 g @ 10…500 Hz IEC 60068-2-6 (Operating) |
Shock (Operating) |
30 g IEC 60068-2-27 (Unpackaged Shock) |
Shock (Non-Operating) |
50 g IEC 60068-2-27 (Unpackaged Shock) |
Emissions |
IEC 61000-6-4 |
ESD Immunity |
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges |
Radiated RF Immunity |
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz |
EFT/B Immunity |
IEC 61000-4-4: ±4 kV @ 2.5 kHz on power ports |
Surge Transient Immunity |
IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports |
Conducted RF Immunity |
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM @ 150 kHz…80 MHz |