Product Description
General Information:
-
Type: Digital Input
-
Signal Specification: NAMUR input level
-
Number of Channels: 8
-
Signal Type: Proximity sensor (NAMUR) or Voltage-free contact
-
Intrinsic Safety: Yes
-
Mechanical Design: S800
Detailed Data:
-
Isolation: Individually isolated, channel-to-channel and to circuit common ground
-
Filter Times: Digital (selectable): 2, 4, 8, 16 ms; Analog filter: 1 ms
-
Current Limiting: Built-in current-limited sensor power
-
Rated Insulation Voltage: 50 V
-
Dielectric Test Voltage: 500 V AC
-
Power Dissipation: 1.4 W
-
Current Consumption:
-
+5 V Modulebus: Typical 120 mA, Maximum <150 mA
-
+24 V external: Typical 50 mA, Maximum <70 mA
-
Diagnostics:
-
Front LEDs: F (Fault), R (Run), W (Warning), Channel 1-8 status and F (Fault)
-
Supervision: Internal process supply and loop supervision
Environment and Certification:
Item | Standard/Requirement |
---|---|
CE Mark | Yes |
Electrical Safety | EN 61010-1, EN 61010-2-201 |
Hazardous Location | ATEX/IECEx Zone 2 with interface to Zone 0, cFMus C1, Div 2/Zone 2 with interface to C1, C2, C3 Div 1/Zone 0 |
Marine Certification | ABS, BV, DNV, 1 LR |
Operating Temperature | 0 to +55 °C (+32 to +131 °F) |
Storage Temperature | -40 to +70 °C (-40 to +158 °F) |
Pollution Degree | Degree 2, IEC 60664-1 |
Corrosion Protection | ISA-S71.04: G3 |
Relative Humidity | 5 to 95%, non-condensing |
Maximum Ambient Temperature | 55 °C (131 °F) for vertical mounting in compact MTU, 40 °C (104 °F) for other mounting |
Protection Class | IP20 according to IEC 60529 |
EMC | EN 61000-6-4, EN 61000-6-2 |
RoHS Compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE Compliance | DIRECTIVE/2012/19/EU |
Compatibility:
-
MTU Use: TU890, TU891
-
Keying Code: AA
Dimensions:
-
Width: 45 mm (1.77”)
-
Depth: 102 mm (4.01”), 111 mm (4.37”) including connector
-
Height: 119 mm (4.7”)
-
Weight: 0.2 kg (0.44 lbs.)