Product Description
🔹 Product Details
Manufacturer |
ICS Triplex |
---|---|
Model/Part Number |
T3411 |
Description |
Monitored Digital Input Module |
🔹 Specifications
Attribute |
Specification |
---|---|
Safetybus Power |
0.85 load units |
Number of Inputs |
16 (common power return) |
Field Power Voltage Range |
15 to 80 VDC |
Field Power Current (max) |
450 mA |
Turn-On Voltage (default) |
> 12 VDC |
Turn-Off Voltage (default) |
< 12 VDC |
Input Current (max) |
5.0 mA |
Turn-On Delay (max) |
10 ms |
Turn-Off Delay (max) |
10 ms |
Overvoltage Protection |
Field: 100 VDC continuousInput: 27 VDC continuous |
Heat Dissipation |
8.5 W / 29 BTU/hr |
Fusing |
Not required (internal resistor limits current to 5 mA) |
Isolation |
2500 V minimum (field wiring to control logic) |
Input Circuit Test Interval |
< 2 seconds (depends on scan time and I/O configuration) |
Intrinsic Safety |
Requires external barrier & threshold adjustment |
🔹 Environmental Specifications
Condition |
Specification |
---|---|
Operating Temperature |
0°C to 60°C (32°F to 140°F) |
Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
Operating Humidity |
0–95% RH, non-condensing |
Vibration |
10–55 Hz: ±0.15 mm |
Shock (Operating) |
15 g, ½ sine wave, 11 ms |
🔹 EMI/EMC Compliance
Standard |
Level / Details |
---|---|
IEC 801 Part 2 |
Level 3: 6 kV contact discharge |
IEC 801 Part 3 |
Level 3: 10 V/m, 27 MHz–500 MHz |
IEC 801 Part 4 |
Level 4: 2 kV, 2.5 kHz, 60 sec |
ANSI/IEEE C37.90 |
2.5 kV damped 1 MHz sine wave |
Fast Transient |
4 kV bi-directional, 10 ns rise time |
🔹 Certifications
Standard |
Details |
---|---|
DIN V VDE 0801 |
Certified for Risk Class 5 |
UL/CSA Compliance |
Designed to meet UL 508 and CSA 22.2 No. 142-M1981 |
🔹 Physical Specifications
Dimension |
Size |
---|---|
Height |
320 mm (12.6 in) |
Width |
32 mm (1.27 in) |
Depth |
257 mm (10.12 in) |
Weight |
1.5 kg (3.3 lbs) |