Product Description
🔹 General Information
Manufacturer |
Allen-Bradley |
---|---|
Model/Part Number |
1734-TBS |
Description |
POINT I/O Terminal Base |
🔹 Technical Specifications
Attribute |
Specification |
---|---|
Field Power Bus Supply Voltage (Max) |
28.8V DC, 120/240V AC |
Field Power Bus Supply Current (Max) |
10 A |
Signal Terminal Voltage |
28.8V DC, 120V/240V AC |
Signal Terminal Current |
2 A |
Enclosure Type Rating |
None (open-style) |
Terminal Base Screw Torque |
0.8 N•m (7 lb•in) |
Wire Size Without End Ferrule |
0.25…2.5 mm² (22…14 AWG) solid or stranded shielded copper wire rated at 75°C (167°F) or greater, 1.2 mm (3/64 in.) insulation max |
Wire Size With End Ferrule |
0.75 mm² (18 AWG) |
🔹 Environmental Specifications
Attribute |
Specification |
---|---|
Operating Temperature |
-20 to +55°C (-4 to +131°F) |
Surrounding Air Temperature (Max) |
55°C (131°F) |
Non-Operating Temperature |
-40 to +85°C (-40 to +185°F) |
Relative Humidity |
5…95% non-condensing (IEC 60068-2-30) |
Vibration |
5 g @ 10…500 Hz (IEC 60068-2-6) |
Shock (Operating) |
30 g (IEC 60068-2-27) |
Shock (Non-Operating) |
50 g (IEC 60068-2-27) |
Emissions |
IEC 61000-6-4 |
ESD Immunity |
IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
Radiated RF Immunity |
IEC 61000-4-3: 10V/m with various frequency ranges |
EFT/B Immunity |
IEC 61000-4-4: ±2 kV at 5 kHz on power and signal ports |
Surge Transient Immunity |
IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports |
Conducted RF Immunity |
IEC 61000-4-6: 10V rms with 1 kHz sine wave 80% AM from 150 kHz…80 MHz |