Product Description
š¹ General Information
Manufacturer |
Allen-Bradley |
---|---|
Model/Part Number |
1734-AENTR/B |
Description |
POINT I/O Ethernet Adapter |
Ā
š¹ Technical Specifications
Attribute |
Value |
---|---|
Indicators |
- 3 red/green status indicators (Module, Network, POINTBus)Ā Ā Ā - 1 green/yellow status indicator (Network activity)Ā Ā Ā - 2 green/yellow indicators (Link 1 & Link 2 activity/status)Ā Ā Ā - 2 green power supply indicators (System power & Field power) |
Power Consumption (Max) |
10.4 W @ 28.8V DC |
Power Dissipation (Max) |
6.3 W @ 28.8V DC |
Thermal Dissipation (Max) |
21.5 BTU/hr @ 28.8V DC |
Input Overvoltage Protection |
Reverse polarity protected |
Isolation Voltage |
50V (continuous), Reinforced Insulation Type, between all circuitsĀ Ā Type tested @ 500V AC for 60s |
Field Power Supply |
10ā¦28.8V DC @ 10A |
Field Power Output |
10ā¦28.8V DC @ 9A |
Module Input |
10ā¦28V DC @ 1000 mA |
POINTBus Output (Max) |
5V DC @ 0.8A |
Ā
š¹ Physical Specifications
Attribute |
Value |
---|---|
Dimensions (HxWxD), Approx. |
76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.) |
Weight, Approx. |
0.28 Kg (0.62 lb) |
Enclosure Type Rating |
None (Open-Style) |
Terminal Base Screw Torque |
0.8 Nm (7 lb-in) |
Ā
š¹ Wiring & Environmental Specifications
Attribute |
Value |
---|---|
Wire Category |
1 ā on power portsĀ Ā 1 ā on communications ports |
Wire Size (Power Connections) |
0.34ā¦2.1 mmĀ² (22ā¦14 AWG) solid or stranded copper wire rated at 75Ā°C (167Ā°F) or greater, 1.2 mm (3/64 in.) insulation maxĀ Ā 90Ā°C (194Ā°F) for ControlLogix |
Ethernet Wiring |
RJ45 connector according to IEC 60603-7Ā Ā 2 or 4 pair Category 5e min cable (TIA 568-B.1)Ā Ā Category 5 cable (ISO/IEC 24702) |
North American Temp Code |
T4 |
ATEX Temp Code |
T4 |
Ā
š¹ Power Supply Specifications
Attribute |
Value |
---|---|
Input Voltage Rating |
24V DC @ 10A |
Input Voltage Range |
10ā¦28.8V DC |
Field Side Power (Max) |
24V DC @ 400 mA |
Inrush Current (Max) |
6 A for 10 ms |
Input Overvoltage Protection |
Reverse polarity protected |
POINTBus Output Current (Max) |
5V DC @ 0.8A |
Interruption Protection |
Output voltage stays within specifications when input drops out for 10 ms @ 10V with max load |
Ā