Product Description
🔹 General Information
Manufacturer |
Allen-Bradley |
---|---|
Model/Part Number |
1715-AENTR/A (EtherNet/IP Adapter) & 1715-A2A (Module Base) |
Description |
1715 Redundant I/O System |
🔹 Technical Specifications
Attribute |
Value |
---|---|
Maximum Modules Supported |
24 per adapter pair |
Operating Voltage Range |
18-32V DC |
Power Requirements |
- 1715-AENTR backplane: 380mA @ 18-32V DC - 1715-A2A input power: 10.4A total max, 400mA max per slot @ 18-32V DC |
Fault-Tolerant Power Limit |
< 3.2A |
Power Dissipation |
8W max per adapter |
Isolation Voltage |
50V (continuous), basic insulation type No isolation between individual Ethernet or DC power ports Type tested @ 500V AC for 60s |
Base Unit |
1715-A2A (2-slot adapter base unit) |
Fuse Type |
4A, 125V, Type T |
🔹 Mechanical Specifications
Attribute |
Value |
---|---|
Weight |
- 1715-AENTR module: 420g (14.82 oz) - 1715-A2A base unit: 283g (9.98 oz) |
Wiring Category |
2 - on power ports 2 - on communication ports |
Wire Size |
- DC Power: Single 2.5 mm² (12 AWG) solid/stranded copper, rated 85°C (185°F), 7mm strip length - Ground Connection: 4 mm² (10 AWG) min |
Wire Type (Ethernet) |
Shielded RJ45 connector (IEC 60603-7) Category 5e min (TIA 568-B.1) or shielded Category 5 (ISO/IEC 24702) |
Enclosure Type |
None (Open-style) |
🔹 Environmental Specifications
Attribute |
Value |
---|---|
Operating Temperature |
-25 to 60°C (-13 to 140°F) |
Maximum Surrounding Air Temperature |
60°C (140°F) |
Non-Operating Temperature |
-40 to 85°C (-40 to 185°F) |
Relative Humidity |
10-95% non-condensing |
Vibration Resistance |
2g @ 10-500Hz (IEC 60068-2-6) |
Shock (Operating) |
- DIN rail mount: 25g - Panel mount: 30g |
Shock (Non-Operating) |
- Installed: 30g - Uninstalled (with slot fillers): 50g |
🔹 EMC & Immunity
Attribute |
Value |
---|---|
Emissions |
CISPR 11 (IEC 61000-6-4) Class A |
ESD Immunity |
IEC 61000-4-2: 6kV contact, 8kV air discharge |
Radiated RF Immunity |
IEC 61000-4-3: 20V/m (80-1000MHz, 1kHz 80% AM) 10V/m (1000-2000MHz, 1kHz 80% AM) 10V/m (900MHz, 200Hz 50% pulse 100% AM) 10V/m (1890MHz, 200Hz 50% pulse 100% AM) 3V/m (2000-2700MHz, 1kHz 80% AM) |
EFT/B Immunity |
IEC 61000-4-4: ±3kV at 5kHz on power ports ±2kV at 5kHz on shielded Ethernet ports |
Surge Transient Immunity |
IEC 61000-4-5: ±1kV line-line (DM), ±2kV line-earth (CM) on power ports ±2kV line-earth (CM) on shielded Ethernet ports |
Conducted RF Immunity |
IEC 61000-4-6: 10V rms (150kHz-80MHz, 1kHz 80% AM) |