- The Triconex 8300A is a Main Power Supply Module designed for Triconex safety instrumented systems (SIS) by Schneider Electric. Belonging to the Triconex Power Modules series, this module provides reliable power to Triconex system components, such as main processors, I/O modules, and communication modules, ensuring continuous operation in triple modular redundant (TMR) architectures. It is critical for safety applications in industries like oil and gas, chemical, and power generation. The 8300A is an updated version of the 8300, offering enhanced performance and compatibility.
Technical Specifications
- The 8300A has the following specifications based on standard characteristics for this model:
Specification | Details |
---|---|
Model/Part Number | 8300A (Assembly 7400127-001) |
Manufacturer | Triconex (Schneider Electric) |
Description | Main Power Supply Module |
Series | Triconex Power Modules |
Input Voltage | 115 VAC/DC (85-140 VAC, 47-63 Hz or 85-150 VDC) |
Output Voltage | 24 VDC |
Power Output | Up to 750 W (system-dependent) |
Redundancy | Supports dual-redundant power supply configurations |
Operating Temperature | -20°C to 70°C (-4°F to 158°F) |
Dimensions | Approx. 5 x 17 x 22 cm |
Weight | Approx. 2 kg |
Additional Details
- The 8300A includes the following additional information based on its standard use and documentation:
- Function: Supplies stable power to Triconex system components, ensuring uninterrupted operation in TMR systems; supports fault-tolerant power distribution with redundant configurations to prevent system downtime.
- Compatibility: Compatible with Triconex Tricon and Tricon CX systems; integrates with mainframes and chassis, powering modules like 3008, 7400209B-030, and I/O modules.
- Configuration: Designed for hot-swappable installation in redundant setups, allowing replacement without system shutdown; includes diagnostic indicators for power status and fault detection.
- Certifications: Meets CE, UL, and IEC 61508 standards for Safety Integrity Level 3 (SIL3) applications; certified for use in hazardous environments.